Free calculator
Commercial kitchen hood CFM calculator
Minimum Type I hood exhaust is calculated per linear foot of hood based on hood style and the heaviest-duty appliance underneath. For a wall-mounted canopy that ranges from 200 CFM per foot (light duty) to 550 CFM per foot (extra-heavy duty) under the International Mechanical Code. Listed hoods may be approved at lower rates by their manufacturer listing.
Minimum exhaust rates (CFM per linear foot)
| Hood type | Light | Medium | Heavy | Extra heavy |
|---|---|---|---|---|
| Wall-mounted canopy | 200 | 300 | 400 | 550 |
| Single island canopy | 400 | 500 | 600 | 700 |
| Double island canopy (per side) | 250 | 300 | 400 | 550 |
| Backshelf / pass-over | 250 | 300 | 400 | Not allowed |
Turn the number into a quote
Send us your result and we'll recommend specific models across brands, with freight-included factory-direct pricing.
Frequently asked questions
How many CFM do I need for a commercial kitchen hood?
For unlisted Type I hoods, the International Mechanical Code sets minimum exhaust rates per linear foot by hood style and appliance duty. For example, a wall-mounted canopy needs 200 CFM/ft over light-duty appliances, 300 over medium-duty, 400 over heavy-duty and 550 over extra-heavy-duty. Listed (UL 710) hoods are often approved at lower rates.
How much make-up air do I need?
Make-up air should replace nearly all of the air you exhaust so the kitchen does not go into strong negative pressure. Many designs supply about 80–90% as dedicated make-up air, with the remainder transferred from the dining room HVAC.
What are light, medium, heavy and extra-heavy duty appliances?
Light duty includes ovens, steamers and kettles; medium duty includes ranges, griddles and fryers; heavy duty includes charbroilers and wok ranges; extra-heavy duty includes solid-fuel appliances such as wood- or charcoal-fired grills and ovens.